Fire Doors
Fire Door Inspections
Annual fire door and smoke door inspections per NFPA 80 — performed by certified technicians with detailed deficiency reports and documentation ready for your Joint Commission or CMS survey.
What We Inspect
Door Clearances & Gaps
Measurement of top, bottom, and side clearances to verify compliance with NFPA 80 tolerances.
Self-Closing & Latching
Verification that doors self-close and latch fully from any open position without manual assistance.
Hardware Condition
Inspection of hinges, closers, coordinators, flush bolts, and all door hardware for damage or improper modification.
Labels & Ratings
Verification that fire door labels are present, legible, and match the required fire rating for the opening.
Frame & Glazing
Assessment of door frames, vision panels, and glazing for damage, improper modifications, or missing components.
Smoke Seals
Inspection of intumescent seals and smoke gasketing for integrity and proper installation.
All doors are tested and documented to NFPA standards located in sections NFPA101-2012: 7.2.1.5.10.1 · 7.2.1.5.11 · 7.2.1.15 | NFPA 80-2010: 4.8.4 · 5.2.1 · 5.2.3 · 5.2.4 · 5.2.6 · 5.2.7 · 6.3.1.7 | NFPA 105-2010: 5.2.1
JGE Inspection Protocol
- 1Labels are clearly visible and legible.
- 2No open holes or breaks exist in surfaces of either the door or frame.
- 3Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped.
- 4The door, frame, hinges and hardware and non-combustible threshold are secured, aligned and in working order with no visible signs of damage.
- 5No parts are missing or broken.
- 6Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7.
- 7The self-closing device is operational; that is, the active door completely closes when operated from the full open position.
- 8If a coordinator is installed, the inactive leaf closes before the active leaf.
- 9Latching hardware operates and secures the door when it is in the closed position.
- 10Auxiliary hardware items, which interfere or prohibit operation, are not installed on the door or frame.
- 11No field modifications to the door assembly have been performed that void the label.
- 12Meeting edge protection, gasketing or edge seals, where required, are inspected to verify their presence and integrity.
- 13Signage affixed to a door meets the requirements listed in 4.1.4.