Fire Dampers

Fire & Smoke Damper Inspections

Comprehensive fire and smoke damper testing per NFPA 80 and NFPA 105 — performed by certified technicians with full documentation and deficiency reporting for your regulatory surveys.

What We Test

Operational Testing

Each damper is cycled to verify it closes fully and reopens correctly, confirming the actuator and blade mechanism are functional.

Access Verification

Confirmation that each damper is accessible for inspection and reset per NFPA requirements.

Blade & Frame Condition

Visual inspection of damper blades, frames, and seals for damage, corrosion, or obstruction.

Fusible Link Inspection

Inspection of fusible links on fire dampers for proper rating, condition, and installation.

Actuator & Controls

Testing of electric and pneumatic actuators on smoke dampers to verify proper operation and control signal response.

Documentation

Complete inspection records for every damper tested, formatted for Joint Commission, CMS, and state survey review.

Dampers are tested and documented to NFPA standards located in sections NFPA 90A-2012: 5.4.8 | NFPA 80-2010: 19.4 | NFPA 105-2010: 6.5 and under installation standards UL555.

JGE Inspection Protocol

  1. 1On first inspection, make sure the damper is not installed backwards. In all cases, the air movement should tend to close the damper. Determine that the access door (if equipped) is reasonably airtight and latches properly.
  2. 2If the damper is closed, check for ruptured fusible links, broken attachment or hinges, damage, corrosion, etc.
  3. 3Ensure the damper is not rusted or blocked; check the hinges and other moving parts.
  4. 4Inspect the fusible link in the fire dampers to ensure proper rating and tensile strength.
  5. 5Check around damper and duct for retaining angle or gap between duct and wall.
  6. 6Check smoke damper distance from wall. No more than 2' distance.
  7. 7Close access doors (if equipped) and check for wind noise.
  8. 8Fill out the fire damper inspection log completely with appropriate comments.
  9. 9Remove the fusible links (where applicable), operate all dampers to verify the damper is self-closing and latches properly. Adjust if necessary. Inspect the fusible link in the fire dampers to ensure proper rating and tensile strength.
  10. 10Ensure the damper is operable with normal system airflow so that they will close and are not held open by the air stream. Dampers must close against the maximum calculated airflow of that portion of the air duct system in which they are installed.
  11. 11Be certain that such tests are run safely and do not damage the system.
  12. 12Lubricate friction points (where needed) and exercise the damper to ensure complete freedom of movement.
  13. 13Ensure the dampers are arranged to close automatically when the system is not in operation.
  14. 14Close access doors and check for wind noise.
  15. 15Fill out the fire damper inspection log completely with appropriate comments.