Fire Dampers
Fire & Smoke Damper Repairs
On-site repair and remediation of failed or deficient fire and smoke dampers — restoring compliance and barrier integrity with minimal disruption to your occupied healthcare facility.
What We Repair
Stuck or Seized Dampers
Freeing and restoring dampers that fail to close or open due to corrosion, debris, or mechanical failure.
Fusible Link Replacement
Replacement of damaged, incorrect, or missing fusible links with properly rated components.
Actuator Repair & Replacement
Repair or replacement of failed electric or pneumatic actuators on smoke and combination dampers.
Blade & Frame Repairs
Repair of bent blades, damaged frames, and compromised seals that prevent proper damper closure.
Access Panel Installation
Installation of access panels where dampers lack proper access for inspection and reset.
Full Damper Replacement
Replacement of dampers that cannot be repaired, with properly rated and listed units.
Dampers are tested and documented to NFPA standards located in sections NFPA 90A-2012: 5.4.8 | NFPA 80-2010: 19.4 | NFPA 105-2010: 6.5 and under installation standards UL555.
JGE Inspection Protocol
- 1On first inspection, make sure the damper is not installed backwards. In all cases, the air movement should tend to close the damper. Determine that the access door (if equipped) is reasonably airtight and latches properly.
- 2If the damper is closed, check for ruptured fusible links, broken attachment or hinges, damage, corrosion, etc.
- 3Ensure the damper is not rusted or blocked; check the hinges and other moving parts.
- 4Inspect the fusible link in the fire dampers to ensure proper rating and tensile strength.
- 5Check around damper and duct for retaining angle or gap between duct and wall.
- 6Check smoke damper distance from wall. No more than 2' distance.
- 7Close access doors (if equipped) and check for wind noise.
- 8Fill out the fire damper inspection log completely with appropriate comments.
- 9Remove the fusible links (where applicable), operate all dampers to verify the damper is self-closing and latches properly. Adjust if necessary. Inspect the fusible link in the fire dampers to ensure proper rating and tensile strength.
- 10Ensure the damper is operable with normal system airflow so that they will close and are not held open by the air stream. Dampers must close against the maximum calculated airflow of that portion of the air duct system in which they are installed.
- 11Be certain that such tests are run safely and do not damage the system.
- 12Lubricate friction points (where needed) and exercise the damper to ensure complete freedom of movement.
- 13Ensure the dampers are arranged to close automatically when the system is not in operation.
- 14Close access doors and check for wind noise.
- 15Fill out the fire damper inspection log completely with appropriate comments.